Technical Bulletin Switchgear with Connected Conductors Operating Above 70oC PDF Print E-mail
Friday, 08 July 2011 05:42

beamaOverview: BS7671 regulation 512.1.2 requires that “Switchgear, protective devices, accessories and other types of equipment shall not be connected to conductors intended to operate at a temperature exceeding 70 °C at the equipment in normal service, unless the equipment manufacturer has confirmed that the equipment is suitable for such conditions”.

BS 7671 regulation; 523.1 (note b) requires that “Where a conductor operates at a temperature exceeding 70 °C, it shall be ascertained that the equipment connected to the conductor is suitable for the resulting temperature at the connection”.

BS 7671 90 °cable tables e.g. Table 4E4, state that; “Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70 °C, the current ratings given in the equivalent table for 70 °C thermoplastic insulated cables (Table 4D4A) must be used (see also Regulation 523.1)”.

Low-voltage switchgear and controlgear assemblies include switchboards, panelboards, distribution boards, busbar trunking systems and consumer units.

Wiring accessories include wall switches, socket-outlets, fused spurs and plugs.

The British (BS) and harmonized standards (BS EN) for these products contain test limits that apply to thermoplastic insulation i.e. PVC, and specifically to low -voltage assemblies, where the terminals of the built-in component e.g. MCCBs / MCBs also contain the terminals for external insulated conductors.

Conclusion
Unless specified by the manufacturer, conductors operating at a temperature exceeding 70 °C are not suitable or safe for use with wiring accessories, low-voltage switchgear and controlgear assemblies. However, 90 °C rated cable can be used for external wiring provided the conductor operating temperature does not exceed 70 °C i.e. where the electrical design is based on current ratings given in the equivalent table for 70 °C thermoplastic insulated cables.

Specifically for a low-voltage switchgear and controlgear assemblies, whenever a declaration states that built-in components (e.g. MCBs / MCCBs) which also contain the terminals for external insulated conductors, are suitable for conductors operating at a temperature exceeding 70 °C, then the components must have been tested in the assembly as part of the appropriate assembly standard.

Contact details

 

Have you any news that would be of interest to others in the industry! or other information that you would like to publicise?
if so why not send us the link and have it added to the site.
For more information Call: 07530 871 673 or Email: info@thepanelbuilder.co.uk

panelbuilder news, panel building, manufacturer,furse, ge power protection, termate

 

Twitter


Newsletter Sign-Up

Subscribe for all the latest Panel Building News
Banner
Banner
Banner
Banner
Banner
Banner